The ventilation performance of an enclosed pig barn depends on fan power and cooling-pad area in the equipment list. In actual operation, however, a more fundamental variable determines whether this equipment can deliver air where it needs to go: whether the building envelope leaks. The airtightness of the building envelope should be tested before a pig barn is used for the first time. This is not optional; it is a prerequisite for determining whether the ventilation system is ready to operate. In a barn with severe air leakage, no matter how fast the fans run, a considerable portion of the “ventilation air” is drawn directly through gaps around doors and windows, pipe penetrations, and ceiling joints. The airflow that actually passes through the pigs’ living area is insufficient.

  There is a fairly direct benchmark for quantifying air leakage: if more than 25% of the minimum ventilation airflow enters through leaks, the ventilation system is not operating optimally. This proportion matters because negative-pressure ventilation is based on the principle that “the air inlets are the main pathways for air to enter the barn.” Once the proportion of leakage becomes too high, the air speed and direction at the inlets can no longer be controlled. In winter, cold air seeps in through gaps from all directions, creating drafts; in summer, cool air from the cooling pads is diluted before it reaches the pig pens. Air leakage rewrites the ventilation “path design” as “air enters wherever there is a leak.” A commonly used method for detecting leaks is a negative-pressure test: close all doors, windows, and controllable air inlets, run the fans at maximum speed, and observe whether the barn can maintain the designed negative pressure, or use smoke tracing to reveal the locations of leaks.

  There are recurring patterns in where air leaks occur. Door gaps are the most common leakage points. Sliding doors are particularly unsuitable for pig houses with negative-pressure ventilation because the gaps between the tracks and door panels are difficult to seal. Windows, holes where pipes pass through walls, and joints between ceilings and walls are also common leakage points. How these areas are treated during construction determines whether they need to be “sealed once” or “patched every year” after the facility goes into operation. Adding weatherstripping when installing doors and windows, filling pipe penetrations with foam or sealant, and applying continuous seals at ceiling-to-wall joints are low-cost measures, but they truly close the “boundary” of the ventilation system. Once airtightness has been properly ensured, the ventilation equipment’s capacity can be fully used to organize airflow inside the pig house, rather than being wasted counteracting leaks everywhere.